Regulator Data Page - ABB C310 Programming Manual

Universal process controllers
Hide thumbs Also See for C310:
Table of Contents

Advertisement

...4 CONFIGURATION

4.4.2 Regulator Data Page

This page is displayed only when
– see Fig. 3.1 and Section 4.10
Control Page
rEGLtr
dAtA
rGL–t
600
dEAdb
1.0
PSN–Fb
INdCtN
SEtUP
PrCESS
14
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
is selected at
bndLESS
.
Page Header – Regulator Data
Regulator Travel Time
This is the time set for the regulator to travel from the fully
open to the fully closed position or from the fully closed to
the fully open position.
Set the value required in seconds, between 1 and 5000
seconds.
Deadband Setting
The deadband is set as a percentage of the engineering
range span to produce a deadband around the control set
point value. This reduces 'hunting' of the regulator.
Set the required value, between 0.0 and 10.0%.
Position Feedback Indication Enable
Select
to enable the
INdCtN
see Section 5.2 of the Operating Guide .
Operating Page –
Select
to disable the
NONE
Note. A value is only displayed in the
if the frame is enabled and the regulator has a feedback
signal.
Return to top of
Regulator Data Page
or
Advance to
Set-up Process Variable Input Page.
frame in the
Control Type
frame in the
Valve Position
frame.
Valve Position
Valve Position
,
Set Up