Replacing Accessible Drives; Required Tools; Preliminary Steps - Fujitsu PRIMERGY TX300 S7 Upgrade And Maintenance Manual

Table of Contents

Advertisement

Accessible drives
12.4

Replacing accessible drives

Upgrade and Repair Units (URU)
Average task duration: 15 minutes

12.4.1 Required tools

Preliminary and concluding steps: tool-less
Replacing accessible drives:
– Slotted screw driver (for bending in or out accessible drive mounting
brackets)

12.4.2 Preliminary steps

Before replacing an accessible drive, perform the following steps:
Ê Locate the desired server as described in section
server" on page
Ê Remove all backup and optical disk media from backup and optical disk
drives as described in section
page
144.
Ê Verify if your backup software solution requires preparative configuration
before starting the procedure as described in section
configuring the backup software solution" on page
Ê Shut down the server as described in section
page
71.
Ê Remove the AC power cords from the PSU cable brackets and disconnect
them from the system as described in section
from the mains" on page
Ê When working on a rack-mounted server, extend it out of the rack as
described in section
684
64.
"Removing backup and optical disk media" on
72.
"Extending the server out of the rack" on page
Upgrade and Maintenance Manual
"Locating the defective
"Verifying and
144.
"Shutting down the server" on
"Disconnecting the server
TX300 S7 / RX350 S7
76.