Hobart 9OC24S Operation Manual page 244

Self-propelled generator set
Table of Contents

Advertisement

GENERATOR
DIVISION
HOBART
BROTHERS
COMPANI
OPERATION,
MJJNTENANcE,
AND
OVERHAUL
MANUAL,
TM-240A
SELF-PROPELLED
GENERATOR
SET',
SPEC.
NO.
5381A
TROUBLE
,SYMPTOM,
AND
CONDITIONS
GENERATOR
(CONTlt'
I n (Continued)
2.
Generator
A. An open or short circuited
operates single
winding
in generator
phase
stator
(GEN )
3.
Generator
over-
heats
4.
Unbalanced
output
PROBABLE
CAUSE
TEST,
CHECK,
AND/OR
REMEDY
B. Open or shorted exciter
rotor winding
(1EXC)
B. Use ohmmeter to check for open
or shorted condition.
If exciter
rotor windings
are good,
proceed
to step C.
C. Open or shorted exciter
m Check field
resistance.
See 2-3,
field
windings
(2FLD)
Fig.
4 for normal values.
D. Open or shorted generator
Da Check resistance
with ohmmeter
rotor
windings
(1 FLD)
to determine
if open or short
circuited
e
Check stator winding
resistances.
See 2-3,
Fig.
4 for normal values.
A. Loose connection
causing
high resistance
Check all output connections
for
looseness.
Look for discoloration
caused by heat.
'highten or re-
place as required.
B.
Improper or blocked venti-
B. Check for foreign
materials
(rags,
lation
etc.)
blocking
air flow.
Provide
adequate ventilation.
C. Generator
stator windings
0 Check statoi
windings.
See 2-3,
short circuited
Fig.
4.
A. Loose connection
in output
Check all output connections.
circuit
Discolored
connectors
indicate
a
loose connection.
Tighten
or re-
place as required.
B. Open or short circuited
stator
phase
B. Check stator
windings
in
accordance
with 2-3,
Para.
2 I
Do
Repair
or replace as required a
C e ,Defective
connection
in output circuit
0 Check plug and receptacle
con-
nectars
at aircraft
e Tighten I
repair,
or replace, as required D
3-2
Page ?8
lrouble
3hooting
Lhart
(bheet
IL4 ot
IY)
Figure
6
Ott
30/73