OPERATION,
MAINTENANCE,
AND
OVERHAUL
MANUAL,
TM-240A
SELF-PROPELLED
GENERATOR
SET,
SPEC.
NO.
5381A
TROUBLE
,SYMPTOM,
AND
CONDITIONS
PROBABLE
CAUSE
TEST.
CHECK.
AND/OR
REMEDY
GENERATOR
AND
EXCITATION
CIRCUIT
(CON TIN UED)
1. (Continued)
B. (Continued)
(5) (Continued)
B. (Continued)
(5) (Con tin ued)
(a)
and exciter
as required.
If
generator
produces a nor-
mal or higher voltage,
see
step (6).
(6) Defective
voltage
regulator
(RE G)
(6)All
components
in the excita-
tion circuit
except the voltage
regulator
have been tested in
steps (1) through
(5) above.
This
leaves only the regulator
as a possible
cause of trouble.
Replace
the complete
voltage
regulator.
LOAD
CON TACTOR
OPERATING
CIRCUIT
1.. Load contactor
A. In addition
to defective
A. Check wiring
and connections
in
(1LC)
will
not
wiring
and connections
the load contactor
circuits
on the
close when load
in the AC and DC load
engine
control
pane I, protective
con tactor
control
contactor
actuating
cir-
switch
(17,
Fig.
relay
tray,
and power module.
cuits,
the load con tactor
Check components as follows:
1) is placed in
may be prevented
from
momentary
ON
closing
for any one of
position.
Gen-
the following
reasons:
erator running
at
norma I output
(1) "Blown " fuse (7FU)
(1)Replace
(7FU).
voltage.
No
fault
lights
on.
(2) Defective
(open) relay
(2)Connect
a jumper lead from
in protective
monitor
terminal
B13,
F,ig. 3 to B20,
(PM).
(l-l,
Fig.
7,
GROUND.
If load contactor
item 1)
will
close when switch
is act-
uated,
replace
protective
mon i tor (PM).
-
Ott
30/73
Trouble
Shooting
Chart
(Sheet
11 of 19)
Figure
6
3-2
Page 21