Hobart 9OC24S Operation Manual page 166

Self-propelled generator set
Table of Contents

Advertisement

YoeART
e
QB
$MOTOR
GENERATOR
DIVISION
a
s
HOBART
BROTHERS
COMPAN"
z
'CF
a-
4. #he
OPERATION,
MAINTENANCE,
AND
OVERHAUL
MANUAL,
TM-240A
SELF-PROPELLED
GENERATOR
SET,
SPEC:.
NO.
5381A
(12)
Check adiustable
voltage
range in automatic
operating
mode.
(a)
Observe
voltmeter
[(30),
Fig.
21 and turn rheostat
(46) CLOCKWISE
to full
clockwise
position.
Maximum
voltage
should be at least 134 V AC,
or
higher .
NOTE:
If voltage
should decrease when the knob is turned clockwise,
it indicates
that internal
wiring
of the voltage
regulator
is in-
correct.
Replace
the complete regulator
tray assembly.
(b)
Observe
voltmeter
and turn rheostat
knob to full
COUNTERCLOCKWISE
position.
Minimum
voltage
should be 108 V AC,
or lower.
(13)
Observe
voltmeter
and adjust rheostat
to obtain
115-V
AC voltmeter
reading.
(14)
Check adiustabl e voltage
range in manual operating
mode.
(a)
Open the generator
control
tray
C(14), Fig.
21 and place the automatic-
manual switch
(33) in MAN UAL
position.
(b)
Observe voltmeter
(30) and turn manual control
rheostat
(31) CLOCKWISE
to full
clockwise
position.
Maximum
voltage
should be at least 160 V AC.
(c)
Observe
voltmeter
and turn rheostat
(31) to full 'COUNTERCLOCKWISE
position.
Minimum
voltage
should be 95 V AC or less.
(d)
Adjust
voltage
to 115 V AC,
then return
the automatic-manual
switch
to AUTOMATIC
position.
(15)
Position
load bank switches,
etc.,
to apply a light
load to the generator.
(16)
Place the load contactor
control
switch
C(17), Fig.
21 in the top,
spring
loaded,
ON position.
Hold
in this position
momentarily.
The indicating
light
(12)
should glow GREEN
and an amperage value should appear on the AC ammeter
(32).
(17)
Release
the switch
(17)
d
I I
an
a ow it to return
to the center
ON
position.
The
load contactor
should open immediately,
and the generator
"on" indicating
light should go OFF.
This
is because the plug interlock
relay
(Ref.
l-l,
Fig.
7,
item 18) is not receiving
power from an outside source of 28 V DC.
It in-
dicates that the plug interlock
contacts
are OPEN
as they should be when the
interlock
coil
is not receiving
28-V
DC power.
(18)
Open the protective
relay tray and place the test bank switch
[(40),
Fig.
21 in
ON
position.
Page 8