Hobart 9OC24S Operation Manual page 169

Self-propelled generator set
Table of Contents

Advertisement

FOBART
8
f
QD
;MOTOR
GENERATOR
DIVISION
e
"b
d
HOBART
BROTHERS
COMPANY
b
. a ,,++
OPERATION,
MAINTENANCE.,.
AND
OVERHAUL
MANUAL,
TM-240A
SELF-PROPELLED
GENERATOR
SET,
SPEC.
NO.
5381A
(36)
Check engine oil pressure at governed
speed (2400 RPM).
Gage should indicate
at least 45 PSI when the engine
is hot.
Check engine coolant
temperature.
Gage should indicate
in the range of 165 degrees to 195 degrees depending
upon ambient
temperature.
(37)
Check ope ra ion of fuse interlock
(Ref.
l-l,
Figure
7,
item 2).
With
unit
t
operating
normally
under load,
remove protective
relay circuit
fuse [Ref.
Figure
2,
item (38)l.
The load contactor
should open immediately.
This
indicates
that the fuse interlock
relay
is functioning
properly.
Replace
fuse and apply load.
NOTE:
Make all protective
relay tests with
the unit operating
under load.
(38)
Check operation
of overvoltage
relay and indicating
light.
(a)
With
the unit running
at normal
load,
adjust thevoltage
regulator
rheo-
stat (46,
Fig.
2) to increase voltage
(turn clockwise)
until
the overvoltage
sensing relay actuates
the protective
monitor
to open the load contactor
and turn on the overvoltage
indicating
light.
The overvoltage
sensing
relay should trip when voltage
reaches
130 V to 134 V.
(b)
Return
unit to normal operating
conditions
by adjusting
voltage
regulator
rheostat
and pressing reset switch
(39).
(39)
Check operation
of undervoltage
sensing relay,
indicating
light,
and time delay.
Before starting
this check,
let us understand
the sequence of events
which
should happen when voltage
is reduced to 103 V or lower.
At some value between
103 V and 93 V,
the undervoltage
sensing relay
(Ref.
l-1,
Fig.
7,
item 5) should
function
to activate
the undervoltage
time delay circuit.
Five
seconds after the
time delay circuit
is activated
(if the undervoltage
condition
continues),
it should
function
to open the protective
monitor
relay
which,
in turn,
will
open the load
con tactor to stop power de I ivery.
As a result
of the action,
the undervoltage
indicating
light
(36) should be turned ON.
A stop watch or sweep-second-hand
watch is required
for this check.
Proceed as follows:
(a)
With
unit running
at normal
load,
use the voltage
regulator
rheostat
(46,
Fig.
2) to reduce voltage
to 104 V.
The load contactor
should NOT
open
after
a 5-second
delay.
(b)
Reduce voltage
in steps of 1 V,
with a delay of at least 5 seconds between
steps.
Restart
stopwatch
or note position
of sweep-second-hand
each time
voltage
is reduced.
At some voltage
value
between
103 V and 93 V,
and
5 seconds after a new voltage
setting
is made, the load contactor
should
be
opened and the undervoltage
indicating
light
should be turned on by the
step-by-step
action
of the undervoltage
sensing relay,
time de lay circuit,
~- --~----~---and-protective- mon-i-tar-relay.
_ .Qct 30/!73
-.-- -. . ..~
-~~.. _,....
..- _... ..__ L.
-. ~.- ..--
.-.~~~- .- ._~_~.. .- . -
. . .
___
. .
_._......
._2.:3

Advertisement

Table of Contents
loading

Table of Contents