1.
Voltage
adjusting
rheostat
2.
Cable length compensation
rheostat
3.
Cable size compensation
rheostat
4.
On-off
switch,
line drop
compensation
5.
Fuse (5 Amp)
6.
Fuse holder
7.
Damp and rate adjustment
potentiometers
Voltage
Regulator
Adjustments
Figure
6
(dd) Apply a ful I load (90 KVA,
260 A) to the generator.
Observe 'AC
voltmeter.
If the voltage
observed
varies
more than 1% (plus or
minus) from 115 V AC,
adjust rheostats
(2) and (3) slightly
to obtain
a voltage
of 115 V AC,
or as close to this
value as possible.
Turn
knobs CLOCKWISE
to INCREASE
voltage
and COUNTERCLOCKWISE
to DECREASE.
Turn each knob a small amount at a time to determine
which rheostat
is having the most effect
on output voltage
and re-
quires adjustment.
(c)
Adjust
"damp" and "rate"
potentiometers
(see Figure
7).
(See 7,
Fig.
6 for potentiometers
location
in voltage
regulator.)
I
Damping
adiustments
are very delicate
and should not be attempted'unless
the generator
output average phase value varies
more than 1 volt,
or
output
voltage
is unstable.
"Damp"
and "rate " adjustments
must be made
-_---
-_--.--...
--in-con.junction~.with.each
other because the.ndjustment.-of-one-may-affect-.
i act