OPERATION,
MAI&ENANCE
AND
OVERHAUL
MANUAL
TM-240A
SELF-PROPELLED
GENERATOR
SET.
SPEC.
NO.
538iA
3-2
Page 20
r
~_
_~~~
TROUBLE,SYMPTOM,
AND
CONDITIONS
PROBABLE
CAUSE
TEST,
CHECK,
AND/OR
REMEDY
GENERATOR
AND
EXCITATION
CIRCUIT
(CONTINUED)
1. (Continued)
B. (Continued)
B. (Continued)
(4) Defective
excitation-
(4)
With
generator
running,
deenergization
relay
place auto-manual
switch
(EDR)
(24,
Fig.
1)
in AUTOMATIC
position.
Connect
a jumper lead
between terminals
Al6
and
ClO,
Fig.
3.
Connect
another
lead between
terminals
Al5
and C9.
If
the generator
will
now pro-
duce a normal voltage,
replace
the excitation-
deenergization
relay
(EDR).
(5) Defective
plug con -
nectar at voltage
reg-
ulator
or defective
wiring
from regulator
to exe iter fie Id
(5)
Before condemning
the volt-
age regulator
as the defec-
tive
component,
eliminate
the plug connector
and wir-
ing as a possible
trouble
source as follows:
(a)Disconnect
Amphenol
connector
(l-l,
Fig.
9,
item 14).
Insert a short
piece of wire
in terminal
"E " of loose connection
(see Fig.
4).
Insert an
another
piece in terminal
"6 " .
Connect
a jumper
lead between the wire
in "E " and a good
GROUND.
Connect
another
jumper between
the wire
in "C'! and +12-
V DC terminal
E8.
If the
generator
will
N OT
pro-
duce a normal voltage,
replace
or repair
Amphe-
nol connector
and wiring
between voltage
regulator
Trouble
Shooting
Chart
(Sheet
10 of 19)
Figure
6
Ott
30/73