4. Engine
will
not
C. (Con tit&d)
C . (Continued)
start.
Cranking
speed n,orma I .
(4) (Continued)
(4) leaking
or damaged condition.
Green
indicating
light
GLOWS
(5) Faulty
installation
(5)Restricted
fitting
missing
from
when engine con'-
return
I ine .
trol
switch
is in
RUN
position
.
(6) Faulty
fuel
pump
(6) Check pump.
Operating
mode
switch
in DRIVE
(a)ReIief
valve not
(a)An
open relief
valve
will
position
(Cont'd)
seating
.
cause low output
pressure.
(b) Worn pump gears
(b)Check
pump for normal
or damaged pump
operation.
Replace
if
drive
defective.
D. Low ambient
temperature,
D. Check causes and remedies
under
or limited
fuel
ENGINE,
Trouble
3, A and B
above .
E.
Low compression
which
E . Check compression.
may be caused by any one
of the following:
(1) Sticking
or burned
(l)Cylinder
head must be remove<
exhaust
va Ives
and overhauled
to correct
this
condition.
(2) Compression
rings worn
or broken
(3) Improper va Ive
c learance adjustment
(2) Check compression.
(3)Check
and adjust valve
clear-
ante
in accordance
with
in-
structions
in Cummins
Opera-
tion and Maintenance