Hobart 9OC24S Operation Manual page 241

Self-propelled generator set
Table of Contents

Advertisement

HOBAR;
I
::
QQ
,MOTOR
GENERATOR
DIVISION
E
"0
2
HOBPlRT
BROTHERS
COMP*NY
6
OPERATION,
M';;iNTENANCE
AND
OVERHAUL
MANUAL
TM-240A
SELF-PROPELLED
GENEdATOR
SET,
SPEC.
NO.
5381A
\
B
AND
CONDITIONS
PROBABLE
CAUSE
TEST,
CHECK,
AND/OR
REMEDY
PROTECTIVE
CIRCUIT
1. Load contactor
A. The overvoltage
condition
A. Press reset switch
(39,
Fig.
1) and
opens during
may have been the result
power delivery.
of a sudden drop in the
resume power delivery.
Observe
Overvoltage
in-
load,
or possible
tampering
voltmeter
(30,
Fig.
1) to be cer-
dicating
light
with
voltage
regulator
rheo-
tain voltage
is normal
115 V AC.
ON.
stat
(46,
Fig.
1), and may
Adjust
to normal
if necessary.
If
have been a normal action.
the load contactor
is opened again
and an overvoltage
condition
is
indicated
by light
(2R) (36,
Fig.
l),
proceed to step B.
B. Defective
overvoltage
sensing relay
(OV)
8. See NOTE
above.
Use voltage
adjusting
rheostat
(46,
Fig.
1)
to reduce voltage
to 110 V AC.
Press reset switch
(39,
Fig.
1)
and resume power delivery.
Ob-
serve voltmeter
and gradually
in-
crease voltage
with
rheostat.
If
the overvoltage
sensing relay.(OV)
functions
to open the load con-
tactor at any value
less than 134 V
AC,
it is defective.
Remove pro-
tective
relay tray and replace.
2.
Load contactor
A. An undervoltage
condition
opens during
A. Observe
generator
voltage
on
caused the undervoltage
power de I ivery.
voltmeter
(VM) and adjust
to
sensing relay
(UV) to func-
kdervoltage
normal
4 15 V AC with
voltage
tion normally.
indicating
light
regulator
rheostat
(46,
Fig.
1).
Resume normal operation.
If
ON.
the load contactor
opens again
and an undervoltage
condition
is indicated
by light
(3R) (35,
Fig.
l),
proceed tostep
B.
B. Defective
undervoltage
B. See NOTE
above.
Press reset
relay
(UV)
switch
(39,
Fig.
1) to turn off in-
dicating
light
(3R).
Use rheostat
(46,
Fig.
1) to reduce voltage
104 V.
The undervoltage
indicat-
ing light should NOT
be turned
on
during a time delay of 5 seconds
or more.
If the light
is turned
on
after
a delay of 5 seconds,
the
Tern .~I. I- c-l- I.
P-1
. IPI
. - -
.- 3-x
Ott
30/73
lrouole
onoormg Lnarr
(xreer
13 of IY)
Figure
6
3-2
Page 25

Advertisement

Table of Contents
loading

Table of Contents