DS1-BD (DS1 Interface Circuit Pack)
Table 233. TEST #144 Slip Alarm Inquiry Test — Continued
Error
Code
Test Result
1 to 88
FAIL
PASS
0
NO BOARD
555-233-119
Description/ Recommendation
The DS1 interface circuit pack detected a slip alarm. The error code equals
the number of slips detected by the DS1 interface circuit pack since the last
slip alarm inquiry test.
1. Retry the command at 1-minute intervals a maximum of 5 times.
2. If the DS1 interface circuit pack is a TN767, enter the list
measurement ds1-log UUCSS command to read the error seconds
measurement.
3. Verify that both endpoints and all intermediate equipment of the DS1
link are administered using the same signaling mode, framing mode,
and line coding.
4. If the DS1 interface circuit pack connects to a T1 facility, call the
vendor of the T1 carrier to diagnose the remote DS1 endpoint. If the
DS1 interface circuit pack connects directly to a switch, call the system
technician of the remote switch to diagnose the DS1 endpoint.
5. Check the active alarm and error logs for recent alarms and errors
against the synchronization (SYNC). Follow the suggested repair
procedure for these errors.
6. Check the physical connectivity of the DS1 pack and of the cable.
7. If this continues to fail, escalate this problem.
No Slip alarm is detected on the DS1 Interface circuit pack.
The test could not relate the internal ID to the port (no board).
This could be due to incorrect translations, no board is inserted, an
incorrect board is inserted, or an insane board is inserted.
1. Check to ensure that the board translations are correct. Use the add
ds1 UUCSS command to administer the DS1 interface if it is not
already administered.
2. If board was already administered correctly, check the error log to
determine if the board is hyperactive. If this is the case, the board is
shut down. Reseating the board will re-initialize the board.
3. If the board was found to be correctly inserted in step 1, issue the
busyout board command.
4. Issue the reset board command.
5. Issue the release busy board command.
6. Issue the test board long command.
This should re-establish the link between the internal ID and the port.
Continued on next page