Specifications - Interlogix ATSx500A Series Installation And Programming Manual

Advisor advanced
Table of Contents

Advertisement

Specifications

For a list of panel models see "List of panel variants" on page iii.
Mains power specifications
Mains input voltage
Current consumption at 230 VAC:
ATS1500A(-IP)
ATS3500A(-IP), ATS4500A-IP
Transformer output:
ATS1500A(-IP)-SM/LP
ATSx500A(-IP)-MM/MM+/LM
ATS3500A(-IP)-LP
Power supply specifications
Power supply type
Power supply voltage [1]
Power supply current:
ATS1500A(-IP)
ATS3500A(-IP)
ATS4500A-IP
Main board consumption:
ATSx500A
ATSx500A-IP
Maximum system current available [2]:
ATS1500A
ATS1500A-IP
ATS3500A
ATS3500A-IP
ATS4500A-IP
Auxiliary power output (AUX. POWER) [3]
Battery power output (BAT) [4]
Battery type
Advisor Advanced ATSx500A(-IP) Installation and Programming Manual
230 VAC +10%, −15%, 50 Hz 10%
300 mA max.
500 mA max.
20 VAC, 31 VA
23 VAC, 58 VA
22 VAC, 53 VA
Type A per EN 50131-6
Type I per VdS 2115
13.8 V
0.2 V
1.10 A max. at 13.8 V
2.10 A max. at 13.8 V
2.65 A max. at 13.8 V
100 mA at 13.8 V
±0.2 V
150 mA at 13.8 V
±0.2 V
1000 mA at 13.8 V
±0.2 V
950 mA at 13.8 V
±0.2 V
2000 mA at 13.8 V
±0.2 V
1950 mA at 13.8 V
±0.2 V
2500 mA at 13.8 V
±0.2 V
13.8 V
0.2 V, 1 A max.
13.8 V
0.2 V, 2.5 A max.
Lead acid rechargeable: [5]
7.2 Ah, 12 V nom. (BS127N)
12 Ah, 12 V nom. (BS130N)
18 Ah, 12 V nom. (BS131N)
26 Ah, 12 V nom. (BS129N)
36 Ah, 12 V nom. (BS134N)
Chapter 2: Installation
0.2 V
0.2 V
0.2 V
35