Interlogix ATSx500A Series Installation And Programming Manual page 81

Advisor advanced
Table of Contents

Advertisement

3. In menu "6.1.n.2 Formula" program the condition filter as below:
#
Event or operand
1>
Keypad.1.7
2
OR
3
Zone.10.1
4
AND
5
Area.1.3
4. In menu "6.2 Outputs" on page 219 set the following values:
- Select filter "Door open" for output 10. Output 10 can then be used to unlock
a door.
- Select Pulsed mode.
- Set Delay time to 00:00'00.
- Set Active time to 00:00'05 s.
Advisor Advanced ATSx500A(-IP) Installation and Programming Manual
Description
Correct PIN, entered on keypad 1.
Active Zone 10, which is connected to the key switch and set up
in "4 Zones and areas" menu.
Area 1 unset.
Chapter 3: System functions