Interlogix ATSx500A Series Installation And Programming Manual page 143

Advisor advanced
Table of Contents

Advertisement

1.2.9.2.m.n Select device
1>Duration [min]
2 Run/Stop test
Select the appropriate device.
1.2.9.2.m.n.1 Duration [min]
1 Test time
> 10<
Set duration (in minutes) for battery test.
Allowed range is 2 to 254.
1.2.9.2.m.n.2 Run/Stop test
2 Run test?
>Yes<
Run battery test.
Test duration is set in "1.2.9.2.m.n.1 Duration [min]" above.
If battery test for this device is already running, you are prompted to stop this
test.
1.2.9.3 Battery replaced
Confirm?
>No<
After replacing the battery the installer should confirm this by using the Battery
replaced menu.
Select Yes and press Enter. The confirmation is displayed for 3 seconds.
INFO
Bat. confirmed
The battery replacement is recorded in the control panel event log.
1.2.10 Panel diag
1>System V/A
2 Battery V
Panel diagnostic allows you to monitor particular electrical data, for example,
current and voltage.
1.2.10.1 System V/A
System voltage:
13.8V
System current:
0.8A
The scrolled screens show the system power supply voltage and current.
Advisor Advanced ATSx500A(-IP) Installation and Programming Manual
Chapter 5: Menu reference
137