8.4.4 Forced set: Off
•
8.4.7 AS fault retry: 15 minutes
•
8.4.8 AS user retry: Disable
See also the appropriate RAS manual for more details.
EN 50136 policy
Required settings:
•
"9.1.n.7 Retry count": 1
•
"9.1.n.8.3.2 Heartbeat time": According Table 30 below.
•
"9.1.n.8.3.5 Freq. HB time": According Table 30 below.
•
"9.3.n.7.1 Firewall": Yes
•
"9.3.n.7.2 Reply on PING": No
•
"9.3.n.7.6.1 Firewall": Yes
•
"9.3.n.7.6.2 Reply on PING": No
•
"9.3.n.9 Encryption": Yes
•
"9.4.3 Encryption key 1" must be set.
See also "Transmitter polling interval requirements" below.
Transmitter polling interval requirements
Transmitter polling interval must be set according to specified requirements for
different alarm transmission systems (ATS). Table 30 below lists all required
settings for the appropriate standards and diallers.
Table 30: Transmitter polling settings
Standard and
Required
category
polling interval
EN 50136:2012
SP2
25 h
SP3
30 min
SP4
3 min
SP5
90 s
SP6
20 s
EN 50136:2010
ATS2 (T2),
25 h
ATS3 (T2)
ATS4 (T3)
300 min
Advisor Advanced ATSx500A(-IP) Installation and Programming Manual
Comm. path and
dialler
PSTN via ATS7700
and GPRS (backup)
via ATS7310
IP built-in, or GPRS
via ATS7310
IP built-in, or GPRS
via ATS7310
IP built-in
IP built-in
PSTN via ATS7700
and GPRS (backup)
via ATS7310
IP built-in, or GPRS
via ATS7310
Chapter 8: Regulations
Option
1.2.6.n.3 Period
9.1.n.8.3.2 Heartbeat time 00:29'00
9.1.n.8.3.2 Heartbeat time 00:02'30
9.1.n.8.3.2 Heartbeat time 00:01'00
9.1.n.8.3.2 Heartbeat time 00:00'10
1.2.6.n.3 Period
9.1.n.8.3.2 Heartbeat time 04:55'00
Required
value
24
24
305