Chapter 5: Menu reference
8.4.3.1 Report BA
1 Report BA
>Yes<
If the Report BA option is set to Yes, in the part set the system reports burglar
alarms triggered during part set to the central station.
8.4.3.2 Access to EE
2 Access to EE
>No<
If the Access to EE option is set to Yes, Access zones become Entry/Exit zones
during part set. Users being inside the premises will then trigger the entry timer
making them aware that the area is set and an unset procedure is required.
8.4.3.3 EE full set
3 EE full set
>No<
If the option is set to Yes and the user exits premises during part set exit time
(which causes activation of entry/exit zone), part set state changes to full set.
Note:
The functionality works only if there is exit time defined for part set. It
means that area part set exit time defined in "4.2.n.2 Exit time" on page 186 must
be longer than 0.
8.4.3.4 PS1 name
8.4.3.5 PS2 name
4 PS1 name
>
<
Use these menus to change the default part set prompts "Part set 1" and "Part
set 2". Empty string is equal to the default prompt.
See Advisor Advanced User Manual for more details on partial setting.
8.4.4 Forced set
3 Forced set
>Off<
The Forced set option enables the forced set feature. The forced set options are
configured below.
Forced set is an option where active zones can automatically be inhibited when
setting an area.
Note:
This option should be used with care. Users may not be aware which
zones are inhibited.
244
Advisor Advanced ATSx500A(-IP) Installation and Programming Manual