Chapter 5: Menu reference
5.1.n.11 Delete door
12 Delete door
>Cancel<
Use the Delete door command to remove the door from the system. To remove
the door, select Ok and press Enter. The door is deleted.
Standard door specific options
5.1.n.8.3.2 Shunt active
2 Shunt active
>Always<
Allows you to choose system status when the door shunt is activated.
Always: The door shunt activates in every system state.
Set: The door shunt is active only if the areas with the selected door are set.
Unset: The door shunt is active only if the areas with the selected door are
unset, or set partially.
5.1.n.8.4 Indication
1>Door held open
No
The menu allows you to configure options for indication of particular access
control events.
5.1.n.8.4.1 Door held open
1 Door held open
>No<
If the option is set to yes, the keypad emits an intermittent signal when the door
is held open longer than the shunt timer (or extended shunt timer) allows it.
5.1.n.8.8 EE Shunt
8 EE Shunt
>No<
If entry/exit shunt is set to E/E 1 or E/E 2, the shunted zone becomes an
entry/exit zone, and door shunt starts the entry/exit 1 timer (or entry/exit 2 timer).
Intelligent door specific options
5.1.n.3.5 Readers opts
1>Card and PIN
>>>
Use the menu to configure readers of the selected door.
204
Advisor Advanced ATSx500A(-IP) Installation and Programming Manual