Interlogix ATSx500A Series Installation And Programming Manual page 240

Advisor advanced
Table of Contents

Advertisement

Chapter 5: Menu reference
8.1.2.2.1 Internal siren
8.1.2.2.2 External siren
Enter the delay time for the internal / external siren. The input format is
hh:mm'ss. The allowed range is from 00:00'00 to 06:00'00.
Caution:
In an unset condition the internal siren delay is ignored and the siren
activates instantly.
8.1.3 System misc opts
The System misc options menu allows you to set up all system programmable
timers.
8.1.3.1 Armed display
1 Armed display
>00'30<
The Armed display delay is a delay before the armed display is activated on the
keypad LCD when it enters the idle state. The input format is mm'ss. The allowed
range is from 00'00 to 10'00.
8.1.3.2 Card and PIN
2 Card&PIN
>00'10<
The Card and PIN menu lets you set the maximum delay time between
presenting the card and entering the PIN (default is 10 seconds). The input
format is mm'ss. The allowed range is from 00'00 to 05'00.
8.1.3.3 Walk test time
3 Walk test time
00'00
The Walk test time menu option defines the maximum time for the walk test (0 to
30 minutes). A value of 00'00 means no limitation, in this case the walk test is
ended only by the user, or when completed successfully. For more information,
see "1.2.5 Walk test" on page 130.
8.1.3.4 Mains reporting delay
4 Mains rep dly
>00:00'00<
The Mains reporting delay option defines the delay time (0 to 4 hours) before a
mains fail is reported to the central station. Enter a value of "0" for immediate
reporting.
234
Advisor Advanced ATSx500A(-IP) Installation and Programming Manual