Interlogix ATSx500A Series Installation And Programming Manual page 135

Advisor advanced
Table of Contents

Advertisement

1.2.5.2.9 Reduced walk
9 Reduced walk
>4h<
Reduced walk test period is a time period before reduced walk test start, in which
particular zone activation excludes this zone from the list of zones being tested.
The following options are available:
4h: Reduced walk test only includes zones that were not active during last
4 hours.
Set2set: Reduced walk test only includes zones that were not active since the
last set.
See "1.2.5.1 Start" on page 127 for more details on reduced walk test.
1.2.5.3 Single zone WT
With reporting
>Yes<
Before walk test starts, you are asked if the reporting to central stations must be
enabled (see "1.2.5.1 Start" on page 127 for details).
Select the input location first (panel, internal or external expander). Then enter
the (physical) input number on this location.
Proceed with walk test for this particular zone the same way as for all zones in a
standard walk test. See "1.2.5.1 Start" on page 127.
1.2.5.4 Test No Bells
4 Test No Bells
>No<
A special walk test mode allows verification of the whole alarm system
functionality. In this mode, a service engineer or a guard must perform as many
actions on the operating alarm system as possible. This may include set and
unset, entry and exit, activating all detectors and tampers. The system operates
as usual, sending all alarm and tamper events to the central station, except none
of system sirens is active.
This allows the central station operator to review all received alarms and verify if
appropriate system functions are working properly.
1.2.5.5 Active walk test
Zone A
>>>
Active walk test allows you to test alarm reporting in case of a confirmed alarm
simulation (required by ACPO).
See "Active walk test" on page 82 for more details.
Advisor Advanced ATSx500A(-IP) Installation and Programming Manual
Chapter 5: Menu reference
129