Chapter 5: Menu reference
The zone resistance is displayed.
Panel 1.1
4.6kOhm
Values above 65 kΩ are considered as open state.
You can now scroll through the list of inputs by pressing Up or Down.
Note:
External expanders (DGP) do not support this functionality.
1.2.1.8 Detector test
1>Duration
10
Detector test functionality allows remote tests of detectors with a dedicated input
test. The menu allows you to configure automatic detector test parameters, or to
run the test manually.
1.2.1.8.1 Duration
1 Duration
>10<
Duration defines how long the test signal is active. The allowed range is 10 to
60 seconds.
1.2.1.8.2 Test time
2 Test time
>00:00<
The time of day the system activates an automatic detector test on.
The allowed range is 00:00 to 23:59, while 00:00 is equal to Off and means that
the automatic test is disabled.
1.2.1.8.3 Test when Set
3 Test when set
>Off<
Defines whether an automatic test is activated or not when the area with the
appropriate detector is set.
1.2.1.8.4 Manual test
4 Manual test
>Cancel<
Change the value to OK and press Enter to activate the detector test manually.
1.2.1.9 Shunt zones
1>Exit Button
Shunt Off
The menu allows you to shunt zones manually.
124