B.6 F: Communication Option Parameters
B.6 F: Communication Option Parameters
u

F6, F7: Communication Option Card

Parameters F6-01 through F6-03 and F6-06 through F6-08 are used for EtherNet/IP, Modbus TCP/IP, and LONWORKS
options. F7 parameters are used for the EtherNet/IP and Modbus TCP/IP options.
No.
(Addr.
Name
Hex)
F6-01
Communications Error
(3A2)
Operation Selection
External Fault from
F6-02
Comm. Option
(3A3)
Detection Selection
External Fault from
F6-03
Comm. Option
(3A4)
Operation Selection
Torque Reference/
F6-06
Torque Limit Selection
(3A7)
from Comm. Option
Multi-Step Speed
F6-07
Enable/Disable
(3A8)
Selection when NefRef/
ComRef is Selected
F6-08
Reset Communication
(36A)
Parameters
<3>
F7-01
(3E5)
IP Address 1
<4> <5>
<6>
F7-02
(3E6)
IP Address 2
<4> <5>
<6>
F7-03
(3E7)
IP Address 3
<4> <5>
<6>
F7-04
(3E8)
IP Address 4
<4> <5>
<6>
F7-05
(3E9)
Subnet Mask 1
<6>
F7-06
(3EA)
Subnet Mask 2
<6>
F7-07
(3EB)
Subnet Mask 3
<6>
F7-08
(3EC)
Subnet Mask 4
<6>
286
LCD Display
Comm Bus Flt Sel
0: Ramp to stop. Decel to stop using the decel time in C1-02.
0: Ramp to Stop
1: Coast to stop.
1: Coast to Stop
2: Fast Stop. Decel to stop using the decel time in C1-09.
2: Fast-Stop
3: Alarm only.
3: Alarm Only
EF0 Detection
0: Always detected.
0: Always Detected
1: Detection during run only.
1: Only During Run
EF0 Fault Action
0: Ramp to stop. Decel to stop using the decel time in C1-02.
0: Ramp to Stop
1: Coast to stop.
1: Coast to Stop
2: Fast Stop. Decel to stop using the decel time in C1-09.
2: Fast-Stop
3: Alarm only.
3: Alarm Only
Torq Ref/Lmt Sel
OLV/PM
OLV/PM
0: Disabled
0: Disabled. Torque reference/limit from option board disabled.
1: Enabled
1: Enabled. Torque reference/limit from option board enabled.
0: Multi-step reference disabled (same as F7)
Fref PrioritySel
1: Multi-step reference enabled (same as V7)
0: Net/Com REF
1: MultiStep Speed
0: Communication-related parameters (F6-oo) are not reset
Com Prm Init Sel
when the drive is initialized using A1-03.
0: Init Com Prms
1: Reset all communication-related parameters (F6-oo) when
1: No Init Com Prms
the drive is initialized using A1-03.
IP Address 1
Sets the most significant octet of network static IP address.
Sets the second most significant octet of network static IP
IP Address 2
address.
IP Address 3
Sets the third most significant octet of network static IP address.
Sets the fourth most significant octet of network static IP
IP Address 4
address.
Subnet Mask 1
Sets the most significant octet of network static Subnet Mask.
Sets the second most significant octet of network static Subnet
Subnet Mask 2
Mask.
Sets the third most significant octet of network static Subnet
Subnet Mask 3
Mask.
Sets the fourth most significant octet of network static Subnet
Subnet Mask 4
Mask.
Description
<1>
<1>
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Values
Page
Default: 1
Range: 0 to 3
Default: 0
Range: 0, 1
Default: 1
Range: 0 to 3
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 192
Min.: 0
Max.: 255
Default: 168
Min.: 0
Max.: 255
Default: 1
Min.: 0
Max.: 255
Default: 20
Min.: 0
Max.: 255
Default: 255
Min.: 0
Max.: 255
Default: 255
Min.: 0
Max.: 255
Default: 255
Min.: 0
Max.: 255
Default: 0
Min.: 0
Max.: 255