d2: Frequency Upper/Lower Limits

Upper and lower frequency limits prevent motor speed from going above or below levels that may cause resonance or
equipment damage.
n
d2-01: Frequency Reference Upper Limit
Sets the maximum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency
references.
Even if the frequency reference is set to a higher value, the drive internal frequency reference will not exceed this value.
No.
d2-01
n
d2-02: Frequency Reference Lower Limit
Sets the minimum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency
references.
If a lower reference than this value is entered, the drive will run at the limit set to d2-02. If the drive is started with a lower
reference than d2-02, it will accelerate up to d2-02.
No.
d2-02
184
d1-05
d1-04
d1-03
(A3)
d1-02
(A2)
d1-01
(A1)
FWD (REV) Run/Stop
ON
ON
ON
Figure 5.27 Preset Reference Timing Diagram
Parameter Name
Frequency Reference Upper Limit
Parameter Name
Frequency Reference Lower Limit
d1-14
d1-13
d1-12
d1-07
d1-06
ON
ON
ON
ON
ON
ON
ON
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
d1-16
d1-15
d1-17
ON
ON
ON
ON
ON
Setting Range
0.0 to 110.0%
Setting Range
0.0 to 110.0%
Time
Default
100.0%
Default
0.0%