D2: Frequency Upper/Lower Limits - YASKAWA CIMR-ZU A Series Programming Manual

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

Frequency Reference 1 (set in b1-01)
Frequency Reference 2
(d1-02 or input terminal A1, A2)
Frequency Reference 3
(d1-03 or input terminal A1, A2)
Frequency Reference 4 (d1-04)
Jog Frequency Reference (d1-17)
<1> The Jog frequency overrides all other frequency references.
d2 Fre uency Upper/Lo er Limits
Upper and lower frequency limits prevent motor speed from going above or below levels that may cause resonance or
equipment damage.
d2 1 Fre uency e erence Upper Limit
Sets the maximum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency
references.
Even if the frequency reference is set to a higher value, the drive internal frequency reference will not exceed this value.
No
d2-01
d2 2 Fre uency e erence Lo er Limit
Sets the minimum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency
references.
If a lower reference than this value is entered, the drive will run at the limit set to d2-02. If the drive is started with a lower
reference than d2-02, it will accelerate up to d2-02.
No
d2-02
able 1 1
Multi Step Speed e erence and erminal S itc Combinations
e erence
<1>
Frequency
reference
FWD (REV) Run/Stop
Multi-step Speed Ref. 1
Multi-step Speed Ref. 2
Jog Reference
Fi ure 1 2
Preset e erence imin Dia ram
Parameter Name
Frequency Reference Upper Limit
Parameter Name
Frequency Reference Lower Limit
Multi Step Speed
Multi Step Speed 2
1
OFF
ON
OFF
ON
d1-04
d1-03
d1-02
(A2)
d1-01
(A1)
d1-17
Time
ON
ON
ON
ON
ON
Settin
Settin
1
d
e erence Settin s
o
1
1
OFF
OFF
ON
ON
an e
De ault
0.0 to 110.0%
100.0%
an e
De ault
0.0 to 110.0%
e erence
OFF
OFF
OFF
OFF
ON
1
0.0%