D: References; D1: Frequency Reference; D2: Frequency Upper/Lower Limits - YASKAWA Z1000 User Manual

Ac drive for hvac fan and pump
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

B.4 d: References
B.4 d: References
Reference parameters set the various frequency reference values during operation.
u

d1: Frequency Reference

No.
(Addr.
Name
Hex)
d1-01
(280)
Frequency Reference 1 Reference 1
d1-02
(281)
Frequency Reference 2 Reference 2
d1-03
(282)
Frequency Reference 3 Reference 3
d1-04
(283)
Frequency Reference 4 Reference 4
d1-16
HAND Frequency
(291)
Reference 1
d1-17
Jog Frequency
(292)
Reference
<1> Range upper limit is determined by parameters d2-01, Frequency Reference Upper Limit, and E1-04, Maximum Output Frequency.
u

d2: Frequency Upper/Lower Limits

No.
(Addr.
Name
Hex.)
d2-01
Frequency Reference
(289)
Upper Limit
d2-02
Frequency Reference
(28A)
Lower Limit
d2-03
Master Speed Reference
(293)
Lower Limit
280
LCD Display
Sets the frequency reference for the drive. Setting units are
determined by parameter o1-03.
Sets the frequency reference for the drive. Setting units are
determined by parameter o1-03.
Sets the frequency reference for the drive. Setting units are
determined by parameter o1-03.
Sets the frequency reference for the drive. Setting units are
determined by parameter o1-03.
Sets the frequency reference for the drive. Setting units are
determined by parameter o1-03.
HAND Freq Ref 1
Sets the Jog frequency reference. Setting units are determined
by parameter o1-03.
Jog Reference
LCD Display
Sets the frequency reference upper limit as a percentage of the
Ref Upper Limit
maximum output frequency.
Sets the frequency reference lower limit as a percentage of the
Ref Lower Limit
maximum output frequency.
Sets the lower limit for frequency references from analog inputs
Ref1 Lower Limit
as a percentage of the maximum output frequency.
Description
Description
YASKAWA TOEP YAIZ1U 03B YASKAWA AC Drive – Z1000 User Manual
Values
Page
Default: 0.00 Hz
Min.: 0.00
165
Max.: 240.00
<1>
Default: 0.00 Hz
Min.: 0.00
165
Max.: 240.00
<1>
Default: 0.00 Hz
Min.: 0.00
165
Max.: 240.00
<1>
Default: 0.00 Hz
Min.: 0.00
165
Max.: 240.00
<1>
Default: 0.00 Hz
Min.: 0.00
165
Max.: 240.00
<1>
Default: 6.00 Hz
Min.: 0.00
165
<1>
Max.: 240.0
Setting
Page
Default: 100.0%
Min.: 0.0
127
Max.: 110.0
Default: 0.0%
Min.: 0.0
127
Max.: 110.0
Default: 0.0%
Min.: 0.0
166
Max.: 110.0