2. ALLEN BRADLEY
Indirect Device Memory Designation
 For the file numbers 0 to 65:
15
n+0
n+1
n+2
n+3
 Specify the file number as well as the element number for the address number.
Example:
Example:
 When specifying an address for the timer (control), counter (control) or control device memory in bit designation, specify
the bit number in decimal notation as shown below:
- T: Timer (control)
DN = 13, TT = 14, EN = 15
- C: Counter (control)
UA = 10, UN = 11, OV = 12, DN = 13, CD = 14, CU = 15
- R: Control
FD = 08, IN = 09, UL = 10, ER = 11, EM = 12, DN = 13, EU = 14, EN = 15
8
7
MSB
LSB
Model
Device type
Address No.
00
Bit designation
00
Station number
When specifying N007:123
Specify "7123" (DEC) for the address number.
When specifying N120:123
Specify "120123" (DEC) for the address number.
120123 (DEC) is equivalent to 1D53B (HEX). Specify "D53B (HEX)" for the lower address number and "0001"
for the higher address number.
 For the file numbers 66 to 255:
0
15
n+0
n+1
n+2
n+3
n+4
8
7
MSB
LSB
Model
Device type
Lower address No.
Higher address No.
00
Bit designation
00
Station number