DP1000G
The communication parameters can be set using keys attached to the digital program controller.
Be sure to match the settings to those made under [Communication Setting] of the editor.
Mode No.
Mode 1
(Operation status
selection)
Mode 8
(Communication
setting)
* To start program operation from the V series, select "COM" for program start method. To select a pattern number from the V series, select
"COM" for pattern selection method.
Notes on parameter change from the V series
Before changing parameters from the V series, function keys and the related mode in the setting menu must be locked
using keys on the digital program controller.
For more information, refer to the instruction manual for the controller issued by the manufacturer.
Available Device Memory
The available setting range of device memory varies depending on the model. Be sure to set within the range available for the
model to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Device Memory
D
(data)
DN
(individual data)
PG
(program)
Address denotations
The assigned device memory is expressed as shown below when editing the screen.
aabbcc
Parameter 2 (BCD)
Parameter 1 (BCD)
Address (BIN)
Note on device memory setting
Do not access addresses that are not assigned in the device memory map.
Item
*
COM: Start by communication
Program start method
*
COM: Selection by communication
Pattern selection method
Fixed according to
Communication type
communication specification
Protocol
PRIVATE: CHINO's conventional protocol
Communication function,
COMM: Host communication
type
Device No.
01 to 99
Baud rate
4800 / 9600 / 19200 / 38400 bps
7N1: data length 7 bits, without parity, stop bit 1
7N2: data length 7 bits, without parity, stop bit 2
7E1: data length 7 bits, even parity, stop bit 1
7E2: data length 7 bits, even parity, stop bit 2
7O1: data length 7 bits, odd parity, stop bit 1
Communication characters
7O2: data length 7 bits, odd parity, stop bit 2
(Data length, parity,
8N1: data length 8 bits, without parity, stop bit 1
stop bit)
8N2: data length 8 bits, without parity, stop bit 2
8E1: data length 8 bits, even parity, stop bit 1
8E2: data length 8 bits, even parity, stop bit 2
8O1: data length 8 bits, odd parity, stop bit 1
8O2: data length 8 bits, odd parity, stop bit 2
TYPE
00H
01H
02H
.........When using one parameter, set "01" for bb (parameter 1).
Example: For DN22 (transmission type), set "DN220100".
7.1 Temperature Controller/Servo/Inverter Connection
Setting
COM1
PORT2
Double-word
Double-word
Double-word
(Underlined setting: default)
Remarks
COM2
When establishing a
connection by using
MODBUS RTU format,
refer to "25. MODBUS".
Invalid during RS-232C
communication
00: Communication not
possible
Remarks
7-3