When Connecting to the Terminal Block on "OPC-VG7-RS" (Optional Communication Board):
Communication setting
Set communication parameters.
Be sure to match the settings to those made under [Communication Setting] of the editor.
Function Code
H30
H31
o37
H40
*1
Available when the communication is enabled by digital input.
Example:
*2
When "FRENIC5000G11S/P11S (MODBUS RTU)" is selected for model selection on the editor, select "Modbus RTU" for the
communication protocol on the inverter.
*3
The communication parameter (data length) is fixed to 8 bits.
Notes on Using "OPC-VG7-RS" (Optional Communication Board)
Set the DIPSW2 on the optional communication board "OPC-VG7-RS" as shown below when connecting the V9 and the
terminal block of the board.
SW2
1
2
OFF
Available Device Memory
The available setting range of device memory varies depending on the model. Be sure to set within the range available for the
model to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Device Memory
4
Item
*1
Link function
Station address
Communication definition
setting
*2
Communication protocol
To make the communication enabled when digital input terminal X1 is turned ON;
Set "24 (link operation)" for function code E01 and turn on the digital input terminal X1 externally.
Terminals from X2 to X9 can also be used. Set the function code corresponding to the digital input terminal to use.
SW2-1
SW2-2
Setting
Setting
OFF
OFF
ON
OFF
Optional communication
OFF
ON
ON
ON
TYPE
02H
16.2 Temperature Controller/Servo/Inverter Connection
Writing of
Monitor/function Data
0
1
2
3
1 to 31
Baud rate
0: 38400 bps
1: 19200 bps
2: 9600 bps
3: 4800 bps
Parity
0: None (stop bit: 2 bits)
1: Even (stop bit: 1 bit)
2: Even (stop bit: 1 bit)
0: FGI-bus
1: SX (loader) protocol
2: Modbus RTU
The underlined settings are set as default.
Function
-
Do not change the default setting
board enabled
when connecting with the V9.
-
(Underlined setting: default)
Setting
Frequency Setting
Operation Command
Remarks
-
-
-
Remarks
16-51
Example
3
1
10
2