Micrex-Sx Sph/Spb Series (Iec Mode) - Hakko Electronics Monitouch V9 Series Connection Manual

Hide thumbs Also See for Monitouch V9 Series:
Table of Contents

Advertisement

16-10
16. Fuji Electric

16.1.4 MICREX-SX SPH/SPB Series (IEC Mode)

Communication Setting
Editor
Communication setting
Item
Connection Mode
Signal Level
Baud Rate
Data Length
Stop Bit
Parity
Target Port No.
PLC
NP1L-RS1, NP1L-RS2, NP1L-RS3, NP1L-RS4, NP1L-RS5
Mode setting
MODE
B C D
A
E
9
F
MODE
8
0
7
1
6
2
5
3
4
* Set the port (or CH No.) where the V9 is connected to "loader".
Communication parameters are fixed to 38400 bps (baud rate), 8 bits (data length), 1 bit (stop bit), and even (parity).
* When the PLC is connected with the V9, the station number setting switch for RS-485 is not used.
1 : 1 / Multi-link2 / Multi-link2 (Ethernet)
RS-232C / RS-422/485
RS1, 2, 4
Setting
RS3, 5
0
General equipment
1
Loader
2
General equipment
3
Loader
4
General equipment
5
Not used
6
Modem loader 19200 bps
7
Self-diagnosis mode 1
8
Self-diagnosis mode 2
9
Modem loader 19200 bps
A
Modem loader 9600 bps
B
Modem loader 9600 bps
C
Modem loader 38400 bps
D
Modem loader 38400 bps
E
Modem loader 76800 bps
F
Modem loader 115200 bps
Setting
38400 bps
8 bits
1 bits
Even
0 to 31
RS-232C Port
CH1
General equipment
General equipment
Loader
Loader
General equipment
General equipment
Loader
General equipment
Loader
General equipment
Loader
General equipment
Modem loader 115200 bps
(Underlined setting: default)
Remarks
For the SPH series:
Do not change the default setting.
RS-485 Port
CH2
RS3 and 5 are not used.
Remarks