4-18
4. Azbil
4.2.10 AHC2001
Communication Setting
Editor
Communication setting
Connection Mode
Signal Level
Baud Rate
Data Length
Stop Bit
Parity
Target Port No.
Controller
CPU unit RS-232C setting
Parameter
Group ID
Type ID
0D2
001
The following settings are fixed; parity: even, and stop bit: 1 bit.
SCU unit setting
Parameter
Group ID
Type ID
001
*1
Exx
002
*1
xx: Unit position 01 to 10H
The unit position varies depending on the mounting position of the SCU unit.
Power
supply
*2
Group ID of port 1 (RS-232C): 001, group ID of port 2 (RS-485): 002
Item
1 : 1 / 1 : n / Multi-link2 / Multi-link2 (Ethernet) /
9600 / 19200 / 38400 / 57600 bps
Item ID
01
Baud rate (port 1)
02
Mode
03
CPL address
Item ID
01
Baud rate
02
Data bit length
03
Parity
*2
04
Stop bit
05
Half duplex / full duplex
07
Protocol selection
CPU
SCU
SCU
E01h
E02h
Setting
1 : n Multi-link2 (Ethernet)
RS-232C / RS-422/485
7/ 8 bits
1 / 2 bits
None / Odd / Even
1 to 31
Setting Items
9600 bps
19200 bps
38400 bps
57600 bps
1: CPL
1 to 31
Setting Items
9600 bps
19200 bps
38400 bps
7: 7 bits
8: 8 bits
0: None
1: Even
2: Odd
1: 1 bit
2: 2 bits
0: Half duplex
1: Full duplex
2: CPL server
(Underlined setting: default)
Remarks
(Underlined setting: default)
Contents
(Underlined setting: default)
Contents
Half duplex: 2-wire connection
Full duplex: 4-wire connection
Invalid during RS-232C
communication
 Unit position E01H - E10H