16-12
16. Fuji Electric
Indirect Device Memory Designation
Specify the CPU number in the expansion code.
PLC_CTL
Macro command "PLC_CTL F0 F1 F2"
Contents
All start
All stop
Operation / standby switching
* Valid only for the redundant system.

16.1.5 MICREX-SX SPH/SPB Series (N Mode / F Mode)

Communication Setting
The communication setting is the same as the one described in "16.1.4 MICREX-SX SPH/SPB Series (IEC Mode)".
Available Device Memory
The available setting range of device memory varies depending on the PLC model. Be sure to set within the range available for
the PLC to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Device Memory
X
(input memory)
Y
(output memory)
M
(standard memory)
L
(retain memory)
SM
(system memory)
*1
Input/output memory does not operate normally unless you import the "*.ini" file created using [Export Device Information] in the PLC
programming tool.
Can be used only for PLC1. Indirect designation is not available.
*2
Double-word addresses (DM, DL, DSM) can be specified only for PLC1.
In the case with PLC2 to PLC8, access to the above addresses is possible when the data length is set to 2 words in the word address (WM,
WL, WSM).
Example: When accessing the address in DM100:
Set the data length to 2 words for WM100.
*3
The assigned device memory is expressed as shown below when editing the screen.
- For X or Y:
- For M, L or SM
Indirect Device Memory Designation
Specify the CPU number in the expansion code.
F0
1 - 8
(PLC1 - 8)
n + 1
1 - 8
(PLC1 - 8)
n + 1
1 - 8
*
n + 1
(PLC1 - 8)
n + 2
TYPE
*1
-
WX as word device, DX as double-word device
*1
-
WY as word device, DY as double-word device
02H
WM as word device, DM as double-word device
04H
WL as word device, DL as double-word device
08H
WSM as word device, DSM as double-word device
F1 (= $u n)
n
Station number: 0000H
Command: 0400H
n
Station number: 0000H
Command: 0402H
n
Station number: 0000H
Command: 040BH
CPU No. operated by default: m (0, 2, 4, 6)
Remarks
Example: X 1 . 00000001 0
Example: M 1 . 00000001 0
*3
*3
*2 *3
*2 *3
*2 *3
Bit address (HEX)
Word address
(F mode: DEC, N mode: HEX)
Period
SX station number
Bit address (HEX)
Word address
(F mode: DEC, N mode: HEX)
Period
CPU No.