Pxr (Modbus Rtu) - Hakko Electronics Monitouch V9 Series Connection Manual

Hide thumbs Also See for Monitouch V9 Series:
Table of Contents

Advertisement

16-26
16. Fuji Electric

16.2.2 PXR (MODBUS RTU)

Communication Setting
Editor
Communication setting
Item
Connection Mode
Signal Level
Baud Rate
Data Length
Stop Bit
Parity
Target Port No.
Temperature Controller
The communication parameter can be set using keys attached to the front of the temperature controller.
Be sure to match the settings to those made under [Communication Setting] of the editor.
Parameter
Third block parameter
*1
The communication function of the temperature controller can be selected at the time of purchase. Select a model on which RS-485
(Modbus) communication is available.
*2
The following communication parameters are fixed; baud rate: 9600 bps, data length: 8 bits, and stop bit: 1 bit.
Available Device Memory
The available setting range of device memory varies depending on the model. Be sure to set within the range available for the
model to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Device Memory
0
1
4
3
Setting
1 : 1 / 1 : n / Multi-link2 /
Multi-link2 (Ethernet) /
1 : n Multi-link2 (Ethernet)
RS-422/485
9600 bps
8 bits
1 bit
None / Even / Odd
1 to 31
Display
Item
STno
Station number
CoM
Parity
PCoL
Communication protocol
TYPE
00H
01H
Read only
02H
03H
Read only
Remarks
Do not change the default settings because these settings on the
temperature controller cannot be changed.
Setting
1 - 31
0: Odd
1: Even
2: None
*1
1: Modbus
2: Z-ASCII
Remarks
(Underlined setting: default)
(Underlined setting: default)
Example
1
0
1