2-28
2. ALLEN BRADLEY
Address denotations
The assigned device memory is expressed as shown below when editing the screen.
 Address other than input/output
- For word access
Nxxx:
The file number will not be displayed for the input, output or status device memory.
 Input/output address
- For word access
I:
Indirect Device Memory Designation
 For the file or slot numbers 0 to 65:
15
MSB
n + 0
Model
n + 1
n + 2
n + 3
 Specify the file number or slot number and the element number for the address number.
Example:
Example:
 When specifying an address for the timer (control), counter (control) or control device memory in bit designation, specify
the bit number in decimal notation as shown below:
- T: Timer (control)
DN = 13, TT = 14, EN = 15
- C: Counter (control)
UA = 10, UN = 11, OV = 12, DN = 13, CD = 14, CU = 15
- R: Control
FD = 08, IN = 09, UL = 10, ER = 11, EM = 12, DN = 13, EU = 14, EN = 15
yyy
Element number
File number
Device type
xxx. yyy
Element number
Slot No.
Device type
8 7
0
LSB
Device type
Address No.
00
Bit designation
00
Station number
When specifying N007:123
Specify "7123" (DEC) for the address number.
When specifying N120:123
Specify "120123" (DEC) for the address number.
120123 (DEC) is equivalent to 1D53B (HEX). Specify "D53B (HEX)" for the lower address number and "0001"
for the upper address number.
For bit access
Nxxx:
yyy/zz
Bit number
Element number
File number
Device type
For bit access
I:
xxx. yyy/zz
Bit number
Element number
Slot No.
Device type
 For the file or slot numbers 66 to 255:
15
MSB
8 7
n + 0
Model
n + 1
Lower address No.
n + 2
Higher address No.
n + 3
00
Bit designation
n + 4
00
Station number
LSB
0
Device type