19-12
19. Hitachi
RS-422/RS-485
Wiring diagram 1 - C4
When connecting to the S10x series, place a resistor of 50 (1/2 W) as shown below.
CN1
Name
Dsub 9 (Male)
1
6
9
5
Wiring diagram 2 - C4
CN1
Name
Dsub 9 (Male)
1
6
9
5
No.
FG
+RD
1
-RD
2
-SD
3
+SD
4
* Use shielded twist-pair cables.
SG
5
No.
FG
+RD
1
-RD
2
-SD
3
+SD
4
* Use shielded twist-pair cables.
SG
5
Name
UTX H
UTX L
50
URX H
50
URX L
No.
Name
Dsub 9 (Female)
-RD
1
+RD
2
9
+SD
3
6
-SD
4
PLC
5