4.2.5
SDC35/36
Communication Setting
Editor
Communication setting
Connection Mode
Signal Level
Baud Rate
Data Length
Stop Bit
Parity
Target Port No.
Controller
CPL communication setting
Item (Bank)
Communication type
(Setup bank)
Device address
(Setup bank)
Baud rate
(Setup bank)
Data type: data length
(Setup bank)
Data type: parity
(Setup bank)
Data type: stop bit
(Setup bank)
Available Device Memory
The available setting range of device memory varies depending on the model. Be sure to set within the range available for the
model to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Device Memory
* The number of times EEPROM can be reprogrammed is limited (approx. 100,000 times). Accordingly, we recommend that
you write such a parameter as to be reprogrammed frequently into RAM, where the number of reprogramming times is
not limited. However, when the parameter has been written into RAM, and the power is turned off and back on again,
data in EEPROM is transferred.
For more information, refer to the instruction manual for the controller issued by the manufacturer.
Item
1 : 1 / 1 : n / Multi-link2 / Multi-link2 (Ethernet) /
4800 / 9600 / 19200 / 38400 bps
Indication
TYPE
---
00H
4.2 Temperature Controller/Servo/Inverter Connection
Setting
1 : n Multi-link2 (Ethernet)
RS-232C / RS-422/485
7 / 8 bits
1 / 2 bits
None / Odd / Even
1 to 31
Setting
C64
0: CPL
C65
1 to 127
0: 4800 bps
1: 9600 bps
C66
2: 19200 bps
3: 38400 bps
0: 7 bits
C67
1: 8 bits
0: Even
C68
1: Odd
2: None
0: 1 bit
C69
1: 2 bits
Without "*": RAM
With "*":
RAM + EEPROM
(Underlined setting: default)
Remarks
(Underlined setting: default)
Remarks
See "20. MODBUS".
Communication is disabled when "0" is set.
Remarks
4-11