Phr (Modbus Rtu) - Hakko Electronics Monitouch V9 Series Connection Manual

Hide thumbs Also See for Monitouch V9 Series:
Table of Contents

Advertisement

16.2.26 PHR (MODBUS RTU)

Communication Setting
Editor
Communication setting
Item
Connection Mode
Signal Level
Baud Rate
Data Length
Stop Bit
Parity
Target Port No.
Recorder
The communication parameters can be set using keys attached to the front of the recorder.
Be sure to match the settings to those made under [Communication Setting] of the editor.
Parameter
Modbus station No.
Modbus baud rate
Modbus parity
Front communication function
*1
The communication function of the recorder can be selected at the time of purchase. Select a model on which RS-485 communication is
available.
*2
The following communication parameters are fixed; data length: 8 bits and stop bit: 1 bit.
Available Device Memory
The available setting range of device memory varies depending on the model. Be sure to set within the range available for the
model to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Device Memory
4
(holding register)
3
(input register)
16.2 Temperature Controller/Servo/Inverter Connection
Setting
1 : 1 / 1 : n / Multi-link2 /
Multi-link2 (Ethernet) /
1 : n Multi-link2 (Ethernet)
RS-422/485
9600 / 19200 bps
8 bits
1 bit
None / Even / Odd
1 to 31
Setting
Example
1 to 31
1
9600 / 19200 bps
19200 bps
None / Even / Odd
Odd
ON / OFF
ON
TYPE
02H
03H
Remarks
Do not change the default settings of the signal level, data
length and stop bit because these settings on the recorder
cannot be changed.
Remarks
Be sure to set to "ON".
Remarks
16-75
(Underlined setting: default)
(Underlined setting: default)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Monitouch v9_series