16-34
16. Fuji Electric
Example of Procedure for Rewriting the Station Number Table
Port No. Setting
Set the port number from
$u0 to 31 on the screen.
$u00000 = 00
$u00001 = 50
$u00002 = 51
:
$u00031 = 81
System Device Memory
The result of [FROM_WR] macro execution is stored in $s728.
[0]: Normal
[1]: Error
Port No. Setting
Write
Write the station number
table in the FP-ROM by the
FRM_WR macro.
[Macro]
FROM_WR $u0000 32
Port No. Setting
Finished
Port No. Setting
Reconnect
Execute reconnection of the
network using the [RESTART]
macro.
[Macro]
$u0050 = 5
RESTART $u50