16.1.3 SPB (N Mode) & FLEX-PC CPU
Communication Setting
Editor
Communication setting
Connection Mode
Signal Level
Baud Rate
Data Length
Stop Bit
Parity
Target Port No.
PLC
SPB, FLEX-PC CPU port
No particular setting is necessary on the PLC.
Built-in RS-232C port on NJ-CPU-B16
On the PLC loader, set parameters for the built-in RS-232C port.
Be sure to match the settings to those made under [Communication Setting] of the editor.
Available Device Memory
The available device memory is the same as the one described in "16.1.2 SPB (N Mode) & FLEX-PC Series".
Item
Setting
1 : 1 / Multi-link2 /
Multi-link2 (Ethernet)
RS-232C / RS-422/485
19200 bps
8 bits
1 bit
Odd
0
16.1 PLC Connection
(Underlined setting: default)
Remarks
When connecting MONITOUCH to the RS-232C port on
NJ-CPU-B16, select [RS-232C]. In other cases, select
[RS-422/485].
16-9