Available Device Memory
The available setting range of device memory varies depending on the PLC model. Be sure to set within the range available for
the PLC to be used. Use [TYPE] when assigning indirect device memory for macro programs.
P100-0
Port 100 - Index group 0
P300-I
Port 300 - Inputs
P300-O
Port 300 - Outputs
P800-I
Port 800 - Inputs
P800-O
Port 800 - Outputs
P800-F
Port 800 - Flags
P801-I
Port 801 - Inputs
P801-O
Port 801 - Outputs
P801-F
Port 801 - Flags
*
Access to the device memory area is not allowed if a password is set for the area.
*1
The addresses are expressed in "bytes". For word designation, specify an even-numbered address.
Address denotations
The assigned device memory is expressed as shown below when editing the screen.
Example: P800 - F00000001
Indirect Device Memory Designation
For P300 / P800 / P801 device memory:
Specify a value obtained by dividing the address by 2. (Discard the fraction.)
Example:
With indirect device memory designation, "9" is assigned for "P300-I00000013".
13 (HEX) = 19 (DEC)
19  2 = 9.5
Device Memory
Index offset
Index group