Programming Guide | VLT® HVAC Drive FC 102
Option
Name
[0]*
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[51]
MCO controlled
[86]
Pressure sensor 1
[88]
Pressure sensor 2
[93]
Pressure sensor 3
[100]
Output freq. 0–100
[101]
Reference min–max
[102]
Feedback +/-200%
[103]
Motor cur. 0–I
[104]
Torque 0–T
[105]
Torque 0–T
[106]
Power 0–P
[107]
Speed 0–HighLim
[113]
Ext. closed loop 1
[114]
Ext. closed loop 2
[115]
Ext. closed loop 3
[186]
Pressure sensor 4
5-68 Pulse Output Max Freq #30/6
Default value:
5000 Hz
Setup:
All setups
Data type:
Uint32
Set the maximum frequency for terminal 27 corresponding to the output variable selected in parameter 5-60 Terminal 27 Pulse Output
Variable.

5-8* I/O Options

6.7.7
5-80 AHF Cap Reconnect Delay
Default value:
25 s
Setup:
2 setups
Data type:
Uint16
© 2024.10
MAX
lim
nom
nom
Description
Select the display output for terminal 27.
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
AU430028034214en-001901 / 130R0310 |
Parameter Descriptions
Range, 0 - 32000 Hz
0
True
Range, 1 - 120 s
0
True
189