Programming Guide | VLT® HVAC Drive FC 102
Shows status and configuration information of the current IoT protocol.
40-9* Security
6.32.7
40-90 UUID
Default value:
Size related
Setup:
1setup
Data type:
VisStr[36]
The Universal Unique Identifier (UUID) identifies this device within the network.
40-92 802.1X Port-Based Network Access Control
Default value:
[0] Disabled
Setup:
All setups
Data type:
Uint8
Use this parameter for setting the protocol used for network port access control using 802.1X.
Option
Name
[0]*
Disable
[1]
Enable EAP-TLS
40-99 Protocol Status Word
Default value:
0
Setup:
1 setup
Data type:
Uint32
This parameter shows the protocol status word for the drive in hex code.
Parameter Group 43-** Unit Readouts
6.33
43-0* Component Status
6.33.1
This parameter group contains read-only information on hardware components in the power section. All parameters in this group are
arrays:
[0]: Power card 1 (the master power card in a parallel drive, or the only power card in a drive with a single inverter section).
l
[1]: Power card 2 (inverter connection in a parallel drive).
l
[2]: Power card 3 (inverter connection in a parallel drive).
l
[3]: Power card 4 (inverter connection in a parallel drive).
l
[4]: Power card 5 (rectifier connection in a parallel drive).
l
[5]: Power card 6 (rectifier connection in a parallel drive).
l
[6]: Power card 7 (rectifier connection in a parallel drive).
l
[7]: Power card 8 (rectifier connection in a parallel drive).
l
[8]: Inrush card (optional).
l
650
| © 2024.10
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Description
Parameter type:
Conversion index:
Change during operation:
Parameter Descriptions
Range, 36 - 36
0
True
Option
–
True
Range, 0 - 0xFFFFFFFF, Array
[10]
0
True
AU430028034214en-001901 / 130R0310