Programming Guide | VLT® HVAC Drive FC 102
Setup:
1 setup
Data type:
Uint32
Set the interval associated with the current preventive maintenance event. This parameter is only used if [1] Running Hours or [2]
Operating Hours is selected in parameter 23-12 Maintenance Base. The timer is reset in parameter 23-15 Reset Maintenance Word.
23-14 Maintenance Date and Time
Default value:
Size related
Setup:
1 setup
Data type:
TimeOfDay
Set the date and time for the next maintenance occurrence if the preventive maintenance event is based on date/time. Date format
depends on the setting in parameter 0-71 Date Format while the time format depends on the setting in parameter 0-72 Time Format.
The drive has no back-up of the clock function. The set date/time is reset to default (2000-01-01 00:00) after a power-down. In
parameter 0-79 Clock Fault, it is possible to program a warning if the clock has not been set properly, for example after a power-
down. Set the time at least 1 hour later than actual time.
When mounting a VLT® Analog I/O option MCB 109 option card, a battery back-up of the date and time is included.
23-15 Reset Maintenance Word
Default value:
[0] Do not reset
Setup:
All setups
Data type:
Uint8
When messages are reset, maintenance item, action, and maintenance date/time are not canceled. Parameter 23-12 Maintenance
Time Base is set to [0] Disabled.
Set this parameter to [1] Do reset to reset the maintenance word in parameter 16-96 Maintenance Word and reset the message shown in
the LCP. This parameter changes back to [0] Do not reset when pressing [OK].
Option
Name
[0]*
Do not reset
[1]
Do reset
23-16 Maintenance Text
Default value:
0
Setup:
1 setup
Data type:
VisStr[20]
526
| © 2024.10
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
NOTICE
NOTICE
Parameter type:
Conversion inde:
Change during operation:
NOTICE
Description
Parameter type:
Conversion index:
Change during operation:
Parameter Descriptions
0
True
Range, 0 - 0, Array [20]
0
True
Option
True
Range, 0 - 20, Array [6]
0
True
AU430028034214en-001901 / 130R0310