Programming Guide | VLT® HVAC Drive FC 102
The drive has no backup of the clock function. The set date/time resets to default (2000-01-01 00:00) after a power-down unless
a real-time clock module with backup is installed. Therefore, the logging is stopped until date/time is readjusted in parameter
-70 Date and Time. In parameter 0-79 Clock Fault, it is possible to program a warning if the clock has not been set properly, for
example, after a power-down.
Select the type of period for logging consumption: [0] Hour of day, [1] Day of week, or [2] Day of month. The counters contain the
logging data from the preprogrammed date/time for start (parameter 23-51 Period Start) and the numbers of hours/days as programmed
for parameter 23-50 Energy Log Resolution. The logging starts on the date programmed in parameter 23-51 Period Start and continues
until 1 day/week/month has passed. The counters contain data for 1 day, 1 week, or 5 weeks back in time and up to the actual time.
The logging starts at the date programmed in parameter 23-51 Period Start. In all cases, the period split refers to operating hours (time
where the drive is powered up).
Option
Name
[0]
Hour of day
[1]
Day of week
[2]
Day of month
[5]*
Last 24 hours
[6]
Last 7 days
[7]
Last 5 weeks
23-51 Period Start
Default value:
Size related
Setup:
2 setups
Data type:
TimeOfDay
When mounting VLT® Analog I/O Option MCB 109, a battery backup of the date and time is included.
Set the date and time at which the energy log starts updating the counters. First, data is stored in counter [00] and starts at the time/date
programmed in this parameter. Date format depends on the setting in parameter 0-71 Date Format and time format on the setting in
parameter 0-72 Time Format.
23-53 Energy Log
Default value:
0
Setup:
All setups
Data type:
Uint32
528
| © 2024.10
NOTICE
Description
Parameter type:
Conversion index:
Change during operation:
NOTICE
Parameter type:
Conversion index:
Change during operation:
Parameter Descriptions
Range, 0 - 0
0
True
Range, 0 - 4294967295, Array
[31]
0
True
AU430028034214en-001901 / 130R0310
Need help?
Do you have a question about the VLT FC 102 and is the answer not in the manual?