Programming Guide | VLT® HVAC Drive FC 102
Select the application response speed if it is known. The default setting is sufficient for most applications. A more precise value decreases
the time needed for carrying out PID adaptation. The setting has no impact on values of parameters and only affects the auto-tuning
speed.
Option
Name
[0]*
Auto
[1]
Fast pressure
[2]
Slow pressure
[3]
Fast temperature
[4]
Slow temperature
20-71 PID Performance
Default value:
[0] Normal
Setup:
All setups
Data type:
Uint8
Select the application response speed if it is known. The default setting is sufficient for most applications. A more precise value decreases
the time needed for carrying out PID adaptation. The setting has no impact on values of parameters and only affects the auto-tuning
speed.
Option
Name
[0]*
Normal
[1]
Fast
20-72 PID Output Change
Default value:
0.10
Setup:
2 setups
Data type:
Uint16
This parameter sets the magnitude of step change during auto tuning. The value is a percentage of full speed. That is, if maximum output
frequency in parameter 4-13 Motor Speed High Limit [RPM]/parameter 4-14 Motor Speed High Limit [Hz] is set to 40 Hz, 0.10 is 10% of
50 Hz, which is 5 Hz. Set this parameter to a value resulting in feedback changes of 10–20% for best tuning accuracy.
20-73 Minimum Feedback Level
Default value:
-999999 ProcessCtrlUnit
Setup:
2 setups
Data type:
Int32
462
| © 2024.10
Description
Takes 30–120 s to complete.
Takes 10–60 s to complete.
Takes 30–120 s to complete
Takes 10–20 minutes to complete.
Takes 30–60 minutes to complete.
Parameter type:
Conversion index:
Change during operation:
Description
Normal setting of this parameter is suitable for pressure control
in fan systems.
Fast setting is used in pumping systems where a faster control
response is wanted.
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter Descriptions
Option
True
Range, 0.01 - 0.5
-2
True
Range, -999999.999 -
999999.999 ProcessCtrlUnit
-2
True
AU430028034214en-001901 / 130R0310

Advertisement

loading
Need help?

Need help?

Do you have a question about the VLT FC 102 and is the answer not in the manual?

Subscribe to Our Youtube Channel

Save PDF