Programming Guide | VLT® HVAC Drive FC 102
36-1* Analog Input X49/1
6.31.2
36-10 Terminal X49/1 Low Voltage
Default value:
0.07 V
Setup:
All setups
Data type:
Int32
Enter the voltage corresponding to the low reference value set in parameter 36-14 Term. X49/1 Low Ref./Feedb. Value.
36-11 Terminal X49/1 Low Current
Default value:
4 mA
Setup:
All setups
Data type:
Int16
Enter the current (mA) corresponding to the low reference value set in parameter 36-14 Term. X49/1 Low Ref./Feedb. Value.
36-12 Terminal X49/1 High Voltage
Default value:
10 V
Setup:
All setups
Data type:
Int16
Enter the voltage corrsponding to the high reference value set in parameter 36-15 Term. X49/1 High Ref./Feedb. Value.
36-13 Terminal X49/1 High Current
Default value:
20 mA
Setup:
All setups
Data type:
Int16
Enter the current (mA) corresponding to the high reference value set in parameter 36-15 Term- X49/1 High Ref./Feedb. Value.
36-14 Terminal X49/1 Low Ref./Feedb. Value
Default value:
0 ReferenceFeedbackUnit
Setup:
All setups
Data type:
Int32
Enter the reference or feedback value (in RPM, Hz, bar, and so on) corresponding to the voltage or current set in parameter 36-10
Terminal X49/1 Low Voltage or parameter 36-11 Terminal X49/1 Low Current.
36-15 Terminal X49/1 High Ref./Feedb. Value
Default value:
100 ReferenceFeedbackUnit
© 2024.10
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
AU430028034214en-001901 / 130R0310 |
Parameter Descriptions
Range, 0 - 10 V
0
True
Range, 0 - 20 mA
-3
True
Range, 0 - 10 V
0
True
Range, 0 - 20 mA
-3
True
Range, -999999.999
- 999999.999
ReferenceFeedbackUnit
0
True
Range, -999999.999
- 999999.999
ReferenceFeedbackUnit
613