Programming Guide | VLT® HVAC Drive FC 102
Option
Name
[0]
Factory setup
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
Active Set-up
0-12 This Set-up Linked to
Default value:
[0] Not linked
Setup:
All setups
Data type:
Uint8
To enable conflict-free changes from 1 setup to another during operation, link setups containing parameters which are not changeable
during operation. The link ensures synchronizing of the not changeable during operation-parameter values when moving from 1 setup
to another during operation. Not changeable during operation-parameters can be identified by the label FALSE in the Change during
operation field. Parameter 0-12 This Set-up Linked to is used by [9] Multi set-up in parameter 0-10 Active Set-up. Multi setup is used to
move from 1 setup to another during operation.
Option
Name
[0]*
Not linked
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
Example
Use multi set-up to shift from setup 1 to setup 2 while the motor is running. Program in setup 1 first, then ensure that setup 1 and setup 2
are synchronized (or linked). Synchronization can be performed in 2 ways:
Select the following options:
l
[2] Set-up 2 in parameter 0-11 Edit Set-up
¢
Set parameter 0-12 This Set-up Linked to to [1] Set-up 1.
¢
© 2024.10
Description
Cannot be changed. It contains the data set and can be used as a
data source when returning the other setups to a known state.
Parameter type:
Conversion index:
Change during operation:
Description
AU430028034214en-001901 / 130R0310 |
Parameter Descriptions
Option
False
55