Programming Guide | VLT® HVAC Drive FC 102
Table 64: Parameter Index
(continued)
45-16.4
45-16.5
45-2* Baseline Settings
6.34.3
Use the parameters in this group to configure how to capture baseline data.
45-20 Type
Default value:
[0] Off
Setup:
All setups
Data type:
Uint8
Use the parameter to select type of baseline computation.
Option
Name
[0]*
Off
[1]
Baseline Run
[2]
Online Baseline
45-21 Status
Default value:
[0] Not started
Setup:
All setups
Data type:
Uint8
This parameter shows the current status of baseline computation.
Option
Name
[0]*
Not started
[1]
Baseline run running
[2]
Online baseline running
[3]
Baseline completed
662
| © 2024.10
Sensor 1 Vibration
Sensor 2 Vibration
Parameter type:
Conversion index:
Change during operation:
Description
Baseline computation type is not set.
Select the option when the application can operate from
minimum to maximum speed in one sweep. On enabling this
option, the condition-based monitoring function sets speed
points. On completion of baseline computation, the motor is
ramped down to 0. The option can only operate when Hand On
mode is set via control panel.
Select the option in applications where baseline run cannot
be utilized. In this type of baseline computation, the drive is
controlled by the application baseline and speed points are
recorded and saved during the duration specified in Parameter
45-24 Duration. The option can only operate when Auto On
mode is set via control panel.
Parameter type:
Conversion index:
Change during operation:
Description
Parameter Descriptions
Option
–
True
Option
–
True