Programming Guide | VLT® HVAC Drive FC 102
Setup:
All setups
Data type:
Uint32
This ramp time is used for deceleration while fire mode is active.
24-42 Timeout for Fire Mode Test
Default value:
10 min
Setup:
All setups
Data type:
Uint8
A digital impulse triggers the fire mode operation with stop on all alarms as option [2] Trip, all alarms/test in parameter 24-09 Fire Mode
Alarms Handling. This test impulse signal can only activate 1 test time period and the normal fire mode operation takes over as soon as
the test time ends, or it stops the test period if the fire mode signal disappears. Only "normal high impulse" signals can trigger the test
timer and test information is included in the LCP and status word, as fire mode output "not operating as expected" is activated.
24-43 Fire Mode Signal Operation
Default value:
Setup:
1 setup
Data type:
Uint8
Ensure that the correct input selections and connections are in place as it is not possible to operation the LCP while fire mode is
activated.
If signal handling is set to inverse, a low [196] FM active and a low [197] FM was active indicate that the drive is off or power
cycling, which can be used to activate a redundant system.
Select how fire mode input and output signals are handled. Before changing this parameter, disable parameter 24-00 Fire Mode
Function.
548
| © 2024.10
Conversion index:
Changes during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
NOTICE
NOTICE
Parameter Descriptions
-2
True
Range, 1 - 60 min
70
True
Option
True
AU430028034214en-001901 / 130R0310

Advertisement

loading
Need help?

Need help?

Do you have a question about the VLT FC 102 and is the answer not in the manual?

Subscribe to Our Youtube Channel

Save PDF