36-34 Terminal X49/5 Low Ref./Feedb. Value
Default value:
0 ReferenceFeedbackUnit
Setup:
All setups
Data type:
Int32
Enter the reference or feedback value (in RPM, Hz, bar, and so on) corresponding to the voltage or current set in parameter 36-30
Terminal X49/5 Low Voltage or parameter 36-31 Terminal X49/4 Low Current.
36-35 Terminal X49/5 High Ref./Feedb. Value
Default value:
100 ReferenceFeedbackUnit
Setup:
All setups
Data type:
Int32
Enter the reference or feedback value (in RPM, Hz, bar, and so on) corresponding to the voltage or current set in parameter 36-32
Terminal X49/5 High Voltage or parameter 36-33 Terminal X49/5 High Current.
36-36 Term. X49/5 Filter Time Constant
Default value:
0.005 s
Setup:
All setups
Data type:
Uint16
Enter the filter time constant. This is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal X49/3. A
high time constant value improves dampening but also increases the time delay through the filter.
36-37 Term. X49/5 Live Zero
Default value:
[1] Enabled
Setup:
All setups
Data type:
Uint8
Use this parameter for either disabling or enabling the live zero monitoring function.
Option
Name
[0]
Disabled
[1]*
Enabled
36-4* Output X49/7
6.31.5
Use the parameters in this group to configure the mode of inputs and outputs of VLT® Programmable I/O Option MCB 115.
© 2024.10
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Description
AU430028034214en-001901 / 130R0310 |
Parameter Descriptions
Range, -999999.999
- 999999.999
ReferenceFeedbackUnit
0
True
Range, -999999.999 -
999999.999
0
True
Range, 0.005 - 10 s
0
True
Option
True