Programming Guide | VLT® HVAC Drive FC 102
Protection Mode
2.3
Once a hardware limit on motor current or DC-link voltage is exceeded, the drive enters protection mode. Protection mode means a
change of the PWM modulation strategy and a low switching frequency to minimize losses. This continues for 10 s after the last fault and
increases the reliability and robustness of the drive while re-establishing full control of the motor.
The following situations cause the drive to enter protection mode:
Undervoltage, the voltage has dropped below the low limit.
l
Overvoltage, the voltage has exceeded the upper limit. Protection mode can be avoided by activating overvoltage control in
l
parameter 2-17 Overvoltage Control. However, activating overvoltage control extends the ramp times.
Overcurrent, the current has exceeded the limit defined in parameter 4-18 Current Limit.
l
Ground fault, a ground fault has appeared.
l
To remove protection mode, set parameter 14-26 Trip Delay at Inverter Fault to 0.
© 2024.10
AU430028034214en-001901 / 130R0310 |