Programming Guide | VLT® HVAC Drive FC 102
Option
Name
[14]
Select preset ref 4
[15]
Select preset ref 5
[16]
Select preset ref 6
[17]
Select preset ref 7
[18]
Select ramp 1
[19]
Select ramp 2
[22]
Run
[23]
Run reverse
[24]
Stop
[26]
DC brake
[27]
Coast
[28]
Freeze output
[29]
Start timer 0
[30]
Start timer 1
[31]
Start timer 2
[32]
Set digital out A low
[33]
Set digital out B low
[34]
Set digital out C low
[35]
Set digital out D low
[36]
Set digital out E low
[37]
Set digital out F low
[38]
Set digital out A high
[39]
Set digital out B high
[40]
Set digital out C high
[41]
Set digital out D high
[42]
Set digital out E high
[43]
Set digital out F high
[60]
Reset counter A
[61]
Reset counter B
© 2024.10
Description
Select preset reference 4.
Select preset reference 5.
Select preset reference 6.
Select preset reference 7. If the active preset reference is
changed, it merges with other preset reference commands
coming from either digital inputs or via fieldbus.
The value is in %.
The value is in %.
Issues a start command to the drive.
Issues a start reverse command to the drive.
Issues a stop command to the drive.
Issues a DC stop command to the drive.
The drive coasts immediately. All stop commands including the
coast command stop the SLC.
Freezes the output frequency of the drive.
Start timer 0, see parameter 13-20 SL Controller Timer for further
description.
Start timer 1, see parameter 13-20 SL Controller Timer for further
description.
Start timer 2, see parameter 13-20 SL Controller Timer for further
description.
Any output with digital output 1 selected is low (off ).
Any output with digital output 2 selected is low (off ).
Any output with digital output 3 selected is low (off ).
Any output with digital output 4 selected is low (off ).
Any output with digital output 5 selected is low (off ).
Any output with digital output 6 selected is low (off ).
Any output with digital output 1 selected is high (closed).
Any output with digital output 2 selected is high (closed).
Any output with digital output 3 selected is high (closed).
Any output with digital output 4 selected is high (closed).
Any output with digital output 5 selected is high (closed).
Any output with digital output 6 selected is high (closed).
Resets counter A to 0.
Resets counter B to 0.
AU430028034214en-001901 / 130R0310 |
Parameter Descriptions
345